Cinque Terre

AAC All Aluminum Conductor Cable

 Tel:+8615003843731

 E-mail:info@giantelectrics.cn

Get a Quote
  Product Description

1.Application: 

OPGW preformed suspension clamp is mainly used to support the suspend OPGW cable. It is suitable for the OPGW cable, conductor and grounding wire on transmission line. It is recommended used on the line with turning angle less than 30 degree.


2.Features: 

2.1.Reasonable distribution of static stress, good endurance capacity for dynamic stress (such as vibration and waving). The grip strength to cable can reach 10%~20% of cable's ultimate tension strength.

2.2. No rigidity contact with cable(conductor), minimum abrasion.

2.3. Excellent materials make the clamp has good elasticity, well tenacity, strong fatigue resistance, well corrosion resistance and long & safe service life.

2.4. Not only protecting cable, its round and smooth outer shape can reduce the corona discharge and electromagnetic loss immensely.

Composition: Inner reinforcing rod, outer rod, rubber insert, suspension housing, grounding wire, etc.


Suspension Camp for OPGW Cable


3.Material of inner reinforcing rods and outer rods: 

Aluminum alloy wires. 

Customers can also choose other linking fittings such as clevis, Eye chain, etc.


4.Specification 

4.1 1.The broken strength: 70KN. The holding strength14%-20%RTS.


TYPE For cable diameter(mm) Outer rods Inner rods code
(root) Diameter(mm) The length of the finished product(mm) (root) Diameter(mm) The length of the finished product(mm)
OXY 1000 70 9 10 11 5.18 1350 11 3.0 1770 Red
OXY 1100 70 10.1 11 12 5.18 1370 12 3.0 1790 Yellow
OXY 1200 70 11.1 12 12 5.18 1390 13 3.0 1810 Blue
OXY 1300 70 12.1 13 13 5.18 1410 14 3.0 1830 Green
OXY 1400 70 13.1 14 13 5.18 1430 15 3.0 1850 Navy Blue
OXY 1500 70 14.1 15 14 5.18 1450 16 3.0 1870 Black
OXY 1600 70 15.1 16 15 5.18 1470 17 3.0 1890 Orange
OXY 1700 70 16.1 17 15 5.18 1490 18 3.0 1910 Purple


4.2 The broken strength: 100KN. The holding strength14%-20%RTS.


TYPE For cable diameter(mm) Outer rods Inner rods code
(root) Diameter(mm) The length of the finished product(mm) (root) Diameter(mm) The length of the finished product(mm)
OXY 1000 100 9 10 11 5.18 1540 10 3.5 1880 Red
OXY 1100 100 10.1 11 12 5.18 1560 11 3.5 1900 Yellow
OXY 1200 100 11.1 12 13 5.18 1580 12 3.5 1920 Blue
OXY 1300 100 12.1 13 13 5.18 1600 12 3.5 1940 Green
OXY 1400 100 13.1 14 14 5.18 1620 13 3.5 1960 Navy Blue
OXY 1500 100 14.1 15 14 5.18 1640 14 3.5 1980 Black
OXY 1600 100 15.1 16 15 5.18 1660 15 3.5 2000 Orange
OXY 1700 100 16.1 17 16 5.18 1680 16 3.5 2020 Purple


4.3 The broken strength:120KN. The holding strength14%-20%RTS.


TYPE For cable diameter(mm) Outer rods Inner rods code
(root) Diameter(mm) The length of the finished product(mm) (root) Diameter(mm) The length of the finished product(mm)
OXY 1300 120 12.1 13 13 5.18 1620 12 3.5 2040 Green
OXY 1400 120 13.1 14 14 5.18 1660 13 3.5 2080 Navy Blue
OXY 1500 120 14.1 15 14 5.18 1700 14 3.5 2120 Black
OXY 1600 120 15.1 16 15 5.18 1740 15 3.5 2160 Orange
OXY 1700 120 16.1 17 16 5.18 1780 16 3.5 2200 Purple